Spread footings

No. 12 · Soil cutaway with footing drain · In the house

In the catalog:Spread footings

Drawing…

A foundation wall standing on a concrete footing, cut open in a block of earth. The footing widens until the soil can carry the wall's load, and it sits below the depth where the ground freezes.

A wall delivers its load in a strip as thin as the wall itself. Soil cannot take that: pressed that hard it squeezes out sideways or compresses until the wall sinks. A spread footing is the widening at the bottom of the wall that fixes this. It is the lowest part of a shallow foundation, and its whole job is to spread the same load over enough ground that the pressure falls to what the soil can safely bear.

Width comes from the soil

01

Every soil has an allowable bearing pressure: the most it may be loaded per unit of area. Divide the load by it and you have the area the footing needs. For a strip footing under a wall, work per foot of wall and the area is simply a width:

B = w ÷ qaB footing width (ft) · w load per foot of wall (lb/ft) · qa allowable bearing pressure (psf)

In the figure a wall carrying 3,000 lb per foot, plus about 580 lb of its own concrete, stands on clay allowed 2,000 psf. It needs a footing at least 1.79 ft wide, which rounds up to 22 in (560). Put the same wall on sand and the arithmetic asks for under 7 in, so a minimum proportion takes over instead. The weight of the wall and footing counts: in cold climates the wall runs deep and can add a quarter to the load.

SoilPresumptive bearingFrost actionDrainage
Well-graded gravel (GW)10,000 psf (479 kPa)NoneExcellent
Well-graded sand (SW)7,500 psf (359 kPa)NoneExcellent
Silty sand (SM)4,000 psf (192 kPa)SlightFair
Inorganic clay (CL)2,000 psf (96 kPa)MediumImpervious
Peat (Pt)UnsuitableSlightPoor

These are presumptive values, conservative figures a code allows when nobody has tested the ground. Codes publish their own tables, often lower than these; on anything bigger than a house, a geotechnical engineer digs test pits or borings and gives a value for the site. Peat and other organic soils have no safe value at all: they are dug out, or the building is carried down through them on piles or caissons.

Proportions

02

Light walls hardly need the formula. For light-frame buildings on stable, granular soil with loads under about 2,000 lb per foot (29 kN/m), the footing can simply be proportioned from the wall:

Wall thickness T
8 in (205) at least, for concrete or masonry carrying up to two floors.
Footing thickness
T, so 8 in (205).
Projection
T/2 each side of the wall, so 4 in (100).
Footing width
2T, so 16 in (405).

Push the footing wider and each projecting toe behaves like a short cantilever, pressed upward by the soil and bending about the face of the wall. Once a toe projects more than half the wall’s thickness, plain concrete is not enough: steel bars run across the bottom of the footing to take the tension. Longitudinal bars run along it in any case, against shrinkage and temperature cracks, with 3 in (75) of concrete between steel and earth. The figure thickens wide footings with their projection as a stand-in for the engineer’s check on shear; real sizes come from that calculation, with concrete of at least 2,500 psi (17 MPa).

Below the frost

03

Water in the ground expands as it freezes, and in silty, wet soil it gathers into lenses of ice that lift whatever rests above. A footing caught in that zone rises in winter and drops in the thaw. So the bottom of every footing is placed below the depth that frost reaches, the frost line, which ranges from nothing in the far south of the United States to five feet and more in the north. This teaching model carries the footing 12 in (305) below that line; a project needs its own foundation and frost-protection design.

Depth alone is not enough. The footing must bear on undisturbed soil, free of roots and organic matter. Where the excavation runs too deep, the ground is made up with engineered fill, compacted in layers of 8 to 12 in (205 to 305) at a controlled moisture content, never with loose spoil.

Pressure in the ground

04

The lines under the footing are pressure bulbs: lines along which the extra vertical stress in the soil is the same fraction of the pressure under the footing, here 80, 60, 40 and 20 percent. The stress spreads sideways as it goes down and thins out. Under the middle of a strip footing it falls to about 55 percent at a depth equal to the footing’s width, 31 percent at twice the width, and 20 percent at three times.

The bulbs scale with the footing. Make the footing twice as wide at the same pressure and it stresses soil twice as deep. That is why a wide footing over a soft layer can settle more than a narrow one, even though its contact pressure is the same. As the soil under load consolidates the building settles: quickly and slightly on dense sand and gravel, slowly and further on clay. What matters most is that it settles evenly, so footings are sized to put the same pressure on the ground everywhere. Uneven, differential settlement is what cracks walls.

The parts around the footing

05
Foundation wall
Cast concrete or concrete block, 8 in (205) at least, standing 6 in (150) or more above finish grade under wood construction. It also resists the push of the soil against it.
Key and dowels
A keyway cast into the footing and steel dowels lock the wall down and resist sliding.
Sill and anchors
A treated 2×6 sill on a strip of sill sealer, held by ½ in (13) bolts set 7 in (180) into the concrete, no more than 6 ft (1830) apart and within 12 in (305) of each end of a sill piece.
Dampproofing
A bituminous coating from 6 in (150) above grade down to the footing; waterproofing where groundwater presses.
Footing drain
A perforated pipe at least 4 in (100) across, bedded in crushed stone with 6 in (150) over it and filter fabric on top, laid to fall to a storm sewer, dry well or open ground.
Finish grade
Sloped away from the wall at 5 percent or more, so surface water never reaches the drain at all.
Crawl space
The ground inside covered with a vapour retarder, the space ventilated to keep the wood dry.

A strip footing under a full-height basement wall is one answer among several. Where frost is shallow the same footing carries a short crawl-space wall or the thickened edge of a slab; where it is deep, insulation laid around a shallow footing can keep the frost out instead of digging below it; and where the soil near the surface cannot carry the house at any width, piers or piles reach down to ground that can. The foundation types figure puts the reference house’s wall on each of them and says when each is the right one, and excavation and backfill builds this footing in its hole, in order.

How the figure decides

06
WidthLarger of 2T (16 in) and total load ÷ allowable pressure, rounded up to 2 in
ThicknessT while the toe projects ≤ T/2; beyond that reinforced and thickened with the projection
Depth12 in (305) below the frost line; never less than 12 in below grade
WeightConcrete at 150 lb/ft³ (23.6 kN/m³) for wall and footing; soil over the toes ignored
BulbsBoussinesq solution for a uniform strip load on an elastic half-space
LimitThe soil block holds footings up to 60 in (1525) wide

Sources & further reading

  1. International Residential Code ↗

    International Code Council · 2024 IRC

    Chapter 4: Foundations; soil bearing, footing dimensions and frost protection. The model's presets are illustrative.

    Background reference for US residential construction. Local adoption and amendments vary; the illustrated model presets are not a statement of code compliance.

A technical review has not yet been recorded for this entry.